Fan Static Pressure Calculator

Walk the duct path section by section — velocity pressure \(p_v=\rho v^2/2\) from airflow and duct size (or typed in directly), friction \(\lambda L/D\) and fitting \(\Sigma\zeta\) losses — and get the fan total pressure FTP = outlet minus inlet total pressure, the fan static pressure FSP = FTP − outlet velocity pressure, and a traffic-light check of the available fan against the system requirement. A pumpXSolver engineering tool.

Total pressure pt Static pressure ps Velocity pressure pv (band + dashed) Fan rise FTP / FSP / pvo

Results — FTP, FSP and the match check

① Air & fan duty — flow, density, available fan

Standard air ρ = 0.0752 lb/ft³ (1.2041 kg/m³). Available FSP = the catalogue fan static pressure at duty.

② Section input basis — geometry or Pd

Diameter basis: each section's velocity follows from Q and D. Pd basis: velocity follows from the typed velocity pressure; D is still used for duct friction (λ·L/D).

③ Duct path sections — losses add along the path

Suction 1 · return → fan inlet
Supply 1 · fan outlet →
Supply 2 · transition 24 → 20 in
Supply 3 · ends at free discharge
Free discharge: the exit velocity pressure of the last section is added automatically — do not enter it as a fitting. Σζ = sum of fitting coefficients (ζ table below the tool).

How it works — three pressures, one Bernoulli chain

Air in a duct carries pressure in two wallets: static \(p_s\) (pushes on the duct wall, does the work) and velocity \(p_v\) (rides in the moving air, recoverable only by decelerating it). Their sum is the total pressure \(p_t\). A fan is sized by accounting for every dollar spent along the path.

1 · The three pressure definitions

$$p_t \;=\; p_s \;+\; p_v \qquad\qquad p_v \;=\; \tfrac{1}{2}\,\rho\,v^{2}\;\;\text{(SI)} \qquad\qquad p_v \;=\; \Bigl(\frac{V}{4005}\Bigr)^{2}\ \text{in-wg}\;\;\text{(US, standard air)}$$

The US shortcut folds ρ = 0.0752 lb/ft³ and the fpm→in-wg conversion into the constant 4005 — e.g. 1,000 fpm → (1000/4005)² ≈ 0.062 in-wg. Bernoulli with losses: total pressure drops only where friction or fittings dissipate energy; static pressure additionally shifts whenever the velocity changes (area change) — acceleration buys \(p_v\) with \(p_s\), deceleration sells it back.

2 · Fan total pressure and fan static pressure

$$\text{FTP} \;=\; p_{t,o} - p_{t,i} \qquad\qquad \text{FSP} \;=\; \text{FTP} - p_{v,o} \qquad\qquad \text{FVP} \;=\; p_{v,o}$$

FTP is the total-pressure rise the fan must produce between inlet and outlet planes. FSP removes the outlet velocity pressure \(p_{v,o}\): with a free discharge, that fraction of the fan's work stays locked in the moving air and never becomes useful static. The classic static method (all static losses + the exit velocity pressure) is conservative — it equals FTP and ignores exactly this \(p_{v,o}\) credit, overpredicting the requirement by \(p_{v,o}\).

3 · Step-by-step build-up along the path

$$v=\frac{4Q}{\pi D^{2}}\quad\text{or}\quad v=\sqrt{2p_v/\rho}\qquad \Delta p_{\text{fric}}=\lambda\,\frac{L}{D}\,p_v\qquad \Delta p_{\text{fit}}=\Sigma\zeta\cdot p_v$$

Each section is evaluated at its own velocity pressure: Darcy friction with a Colebrook λ for galvanized steel (ε ≈ 0.15 mm, standard air), plus the sum of fitting coefficients ζ. Walking the path from ambient (gauge 0) through the suction side, across the fan, and out to the free discharge closes the chain:

$$\text{FTP} \;=\; \sum_{\text{all sections}} \Delta p \;+\; p_{v,\text{exit}} \qquad\Longrightarrow\qquad \text{FSP} \;=\; \sum_{\text{all sections}} \Delta p \;+\; p_{v,\text{exit}} - p_{v,o}$$

4 · Simplified fitting ζ table (reusable)

Fitting (simplified)ζ — multiples of the local pv
45° elbow0.12
90° smooth elbow, r/D = 1.50.15
90° elbow, r/D = 1.0 (5-gore)0.22
90° mitered elbow with turning vanes0.35
90° mitered elbow, no vanes1.20
Tee — branch flow1.00
Sharp-edged entrance (duct from plenum)0.50
Butterfly damper ≈ ⅔ open1.00
Sudden enlargement, area ratio 2:1 (refer to small-duct pv)0.25
Sudden contraction, area ratio 2:10.15

These are engineering estimates for preliminary build-ups — final selections belong on manufacturer data. Fittings in series add: two r/D = 1.0 elbows enter Σζ = 0.44.

5 · Traffic-light thresholds

Margin (available − required) / requiredVerdictAction
🟢 −5% … +15%MatchedNone — healthy, non-wasteful reserve
🟡 +15% … +40%OversizedBalance with dampers or trim speed (VFD)
🔴 > +40%Badly oversizedRe-select the fan or slow it down
🟡 −15% … −5%Slight shortfallCheck filter loading, coil fouling, leakage
🔴 < −15%UndersizedAirflow falls far below design — re-select
Exit kinetic share pv,exit / FTPVerdict
🟢 ≤ 10%Little fan work thrown away at discharge
🟡 10% … 20%Notable — consider a larger end duct or exit cone
🔴 > 20%Dominates — enlarge the final section or add a diffuser

Quick reference — standard air: CFM ↔ fpm ↔ in-wg

Round galvanized duct at three common target velocities. Velocity pressure at those velocities (standard air): 1,000 fpm → 0.062 · 1,500 fpm → 0.140 · 2,000 fpm → 0.249 · 2,500 fpm → 0.390 in-wg.

D (in)A (ft²)cfm @ 1,000 fpmcfm @ 1,500 fpmcfm @ 2,000 fpmcfm @ 2,500 fpm
80.349349524698873
100.5455458181,0911,364
120.7857851,1781,5711,963
141.0691,0691,6042,1382,673
161.3961,3962,0942,7933,491
181.7671,7672,6513,5344,418
202.1822,1823,2724,3635,454
222.6402,6403,9605,2806,600
243.1423,1424,7126,2837,854
284.2764,2766,4148,55210,690
325.5855,5858,37811,17013,963

Same table in SI (v in m/s, Q in m³/h). Velocity pressure: 4 m/s → 9.6 · 6 m/s → 21.7 · 8 m/s → 38.5 · 10 m/s → 60.2 Pa.

D (mm)A (m²)m³/h @ 4 m/sm³/h @ 6 m/sm³/h @ 8 m/sm³/h @ 10 m/s
2500.0497071,0601,4141,767
3150.0781,1221,6832,2442,806
4000.1261,8102,7143,6194,524
5000.1962,8274,2415,6557,069
6300.3124,4896,7338,97811,222
8000.5037,23810,85714,47618,096
10000.78511,31016,96522,61928,274

Symbol table

SymbolMeaningSIHVAC-US
Qairflowm³/scfm
v, Vduct air velocitym/sfpm
Aduct area, πD²/4ft²
ρair density (standard air 1.2041)kg/m³lb/ft³
pv (Pd)velocity (dynamic) pressure, ½ρv²Pain-wg
psstatic pressurePain-wg
pttotal pressure, ps + pvPain-wg
pt,i, pt,ofan inlet / outlet total pressurePain-wg
FTPfan total pressure, pt,o − pt,iPain-wg
FSPfan static pressure, FTP − pv,oPain-wg
pv,ofan outlet velocity pressurePain-wg
λDarcy friction factor (Colebrook, ε ≈ 0.15 mm)
ζfitting loss coefficient, × local pv
L, Dsection length / diametermft, in

Worked anchor — one closed loop (the defaults)

6,000 cfm of standard air, sections as preset (30 ft + 50 ft of 24 in, 40 ft + 30 ft of 20 in, ζ = 0.50 / 0.44 / 0.25 / 0.35), available fan FSP 1.30 in-wg. Every step below reproduces in the calculator; values rounded to 0.001 in-wg (the tool keeps full precision, so re-adding the rounded steps drifts at most ±0.001).

StepQuantityValue
124 in duct area A = πD²/43.142 ft²
2velocity v = 6,000 / 3.1421,910 fpm
3velocity pressure pv = ρv²/2 (24 in sections)0.228 in-wg
420 in duct → v = 2,750 fpm → pv0.472 in-wg
5Suction 1: 30 ft friction + ζ 0.50 · pv0.055 + 0.114 = 0.169
6Supply 1: 50 ft friction + ζ 0.44 · pv0.092 + 0.100 = 0.192
7Supply 2: 40 ft friction + ζ 0.25 · pv0.185 + 0.118 = 0.303
8Supply 3: 30 ft friction + ζ 0.35 · pv0.139 + 0.165 = 0.304
9fan inlet total pt,i−0.169 in-wg
10fan outlet total pt,o = exit pv + supply losses1.270 in-wg
11FTP = 1.270 − (−0.169)1.439 in-wg
12FSP = 1.439 − 0.2281.212 in-wg
13margin vs available 1.30 in-wg → (1.30 − 1.212)/1.212🟢 +7.3% — matched
14exit kinetic share 0.472 / 1.439🔴 32.8% — enlarge the end duct

The loop closes at full precision (4 decimals): FSP + pv,o = 1.2118 + 0.2275 = 1.4393 = FTP = Σ section losses (0.9675) + exit pv (0.4718). The 🔴 exit share is real teaching, not an error — 2,750 fpm at a free discharge burns nearly a third of FTP as jet kinetic energy.